Gas Fired Absorption Heat Pumps

 

The Robur GAHP-W water cooled Absorption Heat Pump is a gas unit providing simultaneously hot water up to 65 °C and chilled water down to 7 °C. The absorption cycle of the Robor GAHP-W is water cooled on both condenser/absorber side and evaporator side, and recovering low temperature heat from water sources (lakes, rivers, ponds, etc.) or ground sources it reaches heating gas efficiencies up to above 150%.

The Robur GAHP-W unit makes a wide variety of convenient applications available, for example:

  • suitable for hotels, hospitals, resorts and spas where consume the central hot water system about 30 cubic meters per day or have more than 80 rooms;
  • low temperature heating systems, where there are available renewable energy sources as lake water, river water or ground water;
  • heating systems recovering heating from heat sources with low/medium temperature (from -2 °C up to 45 °C).

Depending upon needs. Robor GAHP-W can be used in the following way:

  • heating only with heat recovery from a cold source;
  • simultaneous or alternative heating and cooling;

Robur GAHP-W Gas Fired Absorption Heat Pump is available in two different versions:

  • GAHP-W (Water-Water) This version is designed to recovery heat from water sources and to be used when heating and cooling is required simultaneously. This version can produce hot water up to 65 °C and chilled water down to 7 °C.
  • GAHP-W-LB (Ground-Water) This version is designed to recovery heat from the ground. The ground heat can be recovered by using the geothermal - closed loop - system. This ground version can produce chilled water down to -5 °C and hot water up to 60 °C.
HEATING PERFORMANCES(1) GAHP-W
(Water/Water)
GAHP-W-LB
(Ground/Water)(3)
Nominal heating output (water T. inlet 50 °C) kW 38.8 35.0
Outlet chilled water temperature °C 10 0
G.U.E. heating efficiency based on gas consumption % 154 139
Condenser inlet water temperature (min/max) °C 2/45 2/45
Condenser maximum outlet water temperature °C 65 60
COOLING PERFORMANCES(2)
Nominal cooling output (water T. inlet 30 °C) kW 18.4 16.9
Outlet chilled water temperature °C 7 7
G.U.E. cooling efficiency based on gas consumption % 73 67
Evaporator inlet water temperature (min/max) °C 6/45 -2/45
Evaporator minimum outlet water temperature °C 3 -5
GENERAL DATA
Nominal thermal input (burner) kW 25.7
Nominal electrical wattage draw (230 V- 50 Hz) kW 0.54
(1) Nominal conditions according to EN 12309-2 norm. tab 12
(2) Nominal conditions according to EN 12309-2 norm. tab 5
(3) With 25% ethylene glycol in chilled water - evaporator circuit



They have already installed Robur GAHP-W;

 

Rayavadee
Krabi, Thailand

A unit of GAHP-W supplies hot water and chilled water for 77 rooms