Power Quality

How to Supply and Test Data Centre Equipment at 480 V 60 Hz in Thailand

November 18, 2026LEONICS Engineering Team4 min read
How to Supply and Test Data Centre Equipment at 480 V 60 Hz in ThailandPower Quality

The short answer

To run 480 V, 60 Hz equipment from Thailand's three-phase supply you need a frequency converter plus a step-up transformer. The LEONICS FCM-200 (VS) combines both: a 200 kVA modular static frequency converter and a VS-200 cabinet with a transformer and a five-position voltage selector. It takes 380/400/415 V and delivers 357.2, 380, 400, 480 or 508.8 V at 50 or 60 Hz.

In Thailand it is sold and serviced by Leo Power Supply Co., Ltd. (LPS), the LEONICS group distributor.


Check the nameplate first

Thailand's low-voltage three-phase supply is 50 Hz at about 400 V. Three-phase 480 V at 60 Hz is common on equipment built for the North American market. Read the rating plate before choosing anything:

  • Rated for 50/60 Hz and for your supply voltage: no conversion may be needed. Confirm with the equipment maker.
  • Rated for 50/60 Hz but only 480 V: the voltage has to change. Confirm that 50 Hz operation is really allowed at that voltage.
  • Rated for 60 Hz only: the frequency has to change, and a transformer alone cannot do that.

FCM-200 or FCM-200 (VS)

FCM-200FCM-200 (VS)
Rated power200 kVA / 200 kW200 kVA / 200 kW
Power modules4 × 50 kW, hot-swap4 × 50 kW, hot-swap
Input380/400/415 V, 40–70 Hz380/400/415 V, 40–70 Hz
Output voltage (L-L)380 / 400 / 415 V357.2 / 380 / 400 / 480 / 508.8 V
Output frequency50 / 60 Hz ±0.1%50 / 60 Hz ±0.1%
Overall efficiency> 96.5%> 94.0%
Size (W × H × D)60 × 160 × 75 cm140 × 160 × 100 cm
Weight (approx.)270 kg1,070 kg
Choose the FCM-200 when only the frequency has to change. Choose the FCM-200 (VS) when the output voltage has to differ from 380/400/415 V.

Output current of the FCM-200 (VS)

Output (L-L)Phase voltage (L-N)Rated current
357.2 V206 V323 A
380 V219 V304 A
400 V231 V289 A
480 V277 V241 A
508.8 V294 V227 A

Testing equipment at the voltage limits

The FCM-200 (VS) is used as a test supply for data-centre equipment. Three selector positions are nominal ratings and two are a nominal rating with a 6% margin:

Selector positionWhat it is
357.2 V380 V minus 6% (low limit)
380 VNominal
400 VNominal
480 VNominal
508.8 V480 V plus 6% (high limit)
Because 50 or 60 Hz can be selected at every voltage, one unit can run equipment at nominal voltage and at the low and high limits. The voltage is set in steps on the selector switch, not continuously, so check that these values match your test specification.

What to plan for on site

  • Load: add up the real kVA and starting current. The unit runs continuously up to 110%, carries 110–125% for 10 minutes and 125–150% for 1 minute.
  • Floor and space: the FCM-200 (VS) weighs about 1,070 kg. Service is from the front, and cables enter from the top or bottom.
  • Room: rated for 0–40 °C, IP20, forced-air cooling, 72 dBA at 1 metre at full load.
  • Monitoring: USB, RS-232, RS-485 and dry contact, with SNMP/HTTP as an option.
  • Backup power: the FCM converts its input supply, and its specification includes no battery. If the load must ride through an outage, design backup power with it.

Frequently asked questions

Can a transformer alone give me 480 V 60 Hz?

No. A transformer changes voltage but the frequency stays at 50 Hz. Equipment that needs 60 Hz has to be fed through a frequency converter.

Can the FCM-200 (VS) be used as a test power supply?

Yes. It is used to test data-centre equipment at 50 or 60 Hz, at nominal 380, 400 and 480 V, and at 357.2 V (380 V minus 6%) and 508.8 V (480 V plus 6%).

Is the voltage selector available above 200 kVA?

The FCM-200 (VS) brochure covers the 200 kVA model. The FCM-300 to FCM-600 are specified at 380/400/415 V output, so ask LEONICS or LPS about other voltages at those sizes.

Has LEONICS installed FCM units?

Yes. Three FCM-300 units, 900 kVA in total, were installed at the Fabrinet factory in Pathum Thani in 2026. That job feeds production-line machinery, not a data centre.

Who sells and services the FCM in Thailand?

Leo Power Supply Co., Ltd. (LPS), tel +66 2-746-9500 ext. 51, mobile 081-930-2618, LINE @lps.leonics, sales@lpsups.com.

Next step

Send LPS the equipment rating plate, the load in kVA and your supply voltage. See the FCM-Series product page, the data-centre solution and the brochure in downloads.