The short answer
To run 480 V, 60 Hz equipment from Thailand's three-phase supply you need a frequency converter plus a step-up transformer. The LEONICS FCM-200 (VS) combines both: a 200 kVA modular static frequency converter and a VS-200 cabinet with a transformer and a five-position voltage selector. It takes 380/400/415 V and delivers 357.2, 380, 400, 480 or 508.8 V at 50 or 60 Hz.
In Thailand it is sold and serviced by Leo Power Supply Co., Ltd. (LPS), the LEONICS group distributor.
Check the nameplate first
Thailand's low-voltage three-phase supply is 50 Hz at about 400 V. Three-phase 480 V at 60 Hz is common on equipment built for the North American market. Read the rating plate before choosing anything:
- Rated for 50/60 Hz and for your supply voltage: no conversion may be needed. Confirm with the equipment maker.
- Rated for 50/60 Hz but only 480 V: the voltage has to change. Confirm that 50 Hz operation is really allowed at that voltage.
- Rated for 60 Hz only: the frequency has to change, and a transformer alone cannot do that.
FCM-200 or FCM-200 (VS)
| FCM-200 | FCM-200 (VS) | |
|---|---|---|
| Rated power | 200 kVA / 200 kW | 200 kVA / 200 kW |
| Power modules | 4 × 50 kW, hot-swap | 4 × 50 kW, hot-swap |
| Input | 380/400/415 V, 40–70 Hz | 380/400/415 V, 40–70 Hz |
| Output voltage (L-L) | 380 / 400 / 415 V | 357.2 / 380 / 400 / 480 / 508.8 V |
| Output frequency | 50 / 60 Hz ±0.1% | 50 / 60 Hz ±0.1% |
| Overall efficiency | > 96.5% | > 94.0% |
| Size (W × H × D) | 60 × 160 × 75 cm | 140 × 160 × 100 cm |
| Weight (approx.) | 270 kg | 1,070 kg |
Output current of the FCM-200 (VS)
| Output (L-L) | Phase voltage (L-N) | Rated current |
|---|---|---|
| 357.2 V | 206 V | 323 A |
| 380 V | 219 V | 304 A |
| 400 V | 231 V | 289 A |
| 480 V | 277 V | 241 A |
| 508.8 V | 294 V | 227 A |
Testing equipment at the voltage limits
The FCM-200 (VS) is used as a test supply for data-centre equipment. Three selector positions are nominal ratings and two are a nominal rating with a 6% margin:
| Selector position | What it is |
|---|---|
| 357.2 V | 380 V minus 6% (low limit) |
| 380 V | Nominal |
| 400 V | Nominal |
| 480 V | Nominal |
| 508.8 V | 480 V plus 6% (high limit) |
What to plan for on site
- Load: add up the real kVA and starting current. The unit runs continuously up to 110%, carries 110–125% for 10 minutes and 125–150% for 1 minute.
- Floor and space: the FCM-200 (VS) weighs about 1,070 kg. Service is from the front, and cables enter from the top or bottom.
- Room: rated for 0–40 °C, IP20, forced-air cooling, 72 dBA at 1 metre at full load.
- Monitoring: USB, RS-232, RS-485 and dry contact, with SNMP/HTTP as an option.
- Backup power: the FCM converts its input supply, and its specification includes no battery. If the load must ride through an outage, design backup power with it.
Frequently asked questions
Can a transformer alone give me 480 V 60 Hz?
No. A transformer changes voltage but the frequency stays at 50 Hz. Equipment that needs 60 Hz has to be fed through a frequency converter.Can the FCM-200 (VS) be used as a test power supply?
Yes. It is used to test data-centre equipment at 50 or 60 Hz, at nominal 380, 400 and 480 V, and at 357.2 V (380 V minus 6%) and 508.8 V (480 V plus 6%).Is the voltage selector available above 200 kVA?
The FCM-200 (VS) brochure covers the 200 kVA model. The FCM-300 to FCM-600 are specified at 380/400/415 V output, so ask LEONICS or LPS about other voltages at those sizes.Has LEONICS installed FCM units?
Yes. Three FCM-300 units, 900 kVA in total, were installed at the Fabrinet factory in Pathum Thani in 2026. That job feeds production-line machinery, not a data centre.Who sells and services the FCM in Thailand?
Leo Power Supply Co., Ltd. (LPS), tel +66 2-746-9500 ext. 51, mobile 081-930-2618, LINE @lps.leonics, sales@lpsups.com.Next step
Send LPS the equipment rating plate, the load in kVA and your supply voltage. See the FCM-Series product page, the data-centre solution and the brochure in downloads.